The physical phenomena associated with stator winding insulation condition as detected by the ramped direct high-voltage method

Posted on:2005-12-05Degree:Ph.DType:Dissertation
University:Mississippi State UniversityCandidate:Rux, Lorelynn MaryFull Text:PDF
GTID:1452390008483770Subject:Engineering
Abstract/Summary:
Deregulation of the electric utility industry has increased the need to monitor the state of powerplant equipment, such as critical generators and motors, to improve availability and reduce life cycle costs via condition-based maintenance. To achieve these goals, nondestructive condition assessment and diagnostic tests are necessary to evaluate the quality and condition of a machine's stator winding insulation system. Periodic tests are generally conducted to monitor insulation aging, diagnose problems, or provide some assurance that the winding has a minimum level of electrical strength.; The basic principles of insulation testing are presented herein, and the physical mechanisms that affect the current versus voltage response are described. A stator winding insulation model was developed based on this theoretical foundation for use in understanding and analyzing the macroscopic behavior of complex insulation phenomena.; A comprehensive, controlled laboratory experiment was conducted on a set of stator coils that were deliberately manufactured with and without insulation defects. Specific defects were chosen to represent the types of insulation problems typically encountered during manufacture or as a result of in-service aging, and included lack of resin cure, loosely-applied insulating tapes, internal conductive contamination, reduced density of the groundwall insulation, and thermal cycling damage. Results are presented from a series of electrical tests conducted on the coil specimens to compare the effectiveness of various test methods in detecting the different insulation problems. The tests included insulation resistance, polarization index, ramped direct voltage, dissipation factor, dielectric spectroscopy, partial discharge, and recovery voltage measurements.; Dielectric principles and testing experience obtained during this investigation were applied to a collection of test results obtained by the author from in-service machines during the past ten years. These results and analyses provide a practical illustration of the ability of the ramped direct high-voltage test method to distinguish between normal insulation and that with problems, and to help identify the cause and extent of the deficiencies. While no single diagnostic method is ideally suited to detect all possible stator winding insulation problems, ramped voltage tests are shown to be useful in determining when corrective actions are needed and what the appropriate actions are.
Keywords/Search Tags:Stator winding insulation, Voltage, Ramped direct, Tests, Condition
Related items