Dynamic Power Flow Control for a Smart Micro-grid by a Power Electronic Transformer

Posted on:2012-10-27Degree:Ph.DType:Dissertation
University:University of MinnesotaCandidate:Shah, Jalpa KaushilFull Text:PDF
GTID:1452390008492663Subject:Engineering
Abstract/Summary:
A novel strategy, for control of the power flow for a smart micro-grid is proposed. The utility grid power is dynamically controlled by a Power Electronic Transformer (PET). A 60 Hz, step-down transformer is generally used at the point of common coupling (PCC), to connect the micro-grid to the power system grid. Substitution of the conventional 60Hz transformer, by a PET, results in enhanced micro-grid power management system, during grid-connected operation. The smart micro-grid is a set of controllable loads and distributed energy resources (DER); both renewable and non-renewable; that supply demand of a group of customers. The proposed dynamic power limiter (also referred to as PET) is a high-frequency, isolated power-converter system, comprised of a high-frequency step-down transformer and three-phase to single-phase matrix converters. The matrix converters are modulated with a novel pulse width modulation (PWM) strategy for a bi-directional power flow control. The output of the matrix converter generates a high frequency (few kHz) pulsating single phase AC at the primary and secondary of the transformer, which are phase shifted for active power control. The PET also allows voltage regulation by control of reactive power. The entire system; represented as two, three-phase AC systems with an intermediate high-frequency transformer; is simulated using Matlab/Simulink. The equivalent system has utility grid at the input side and a micro-grid on the output side. The micro-grid is modeled as an interconnected system consisting of set of DERs and smart loads. The simulation analyzes the change in micro-grid's power generation and consumption in response to the change in its local grid frequency, upon limiting the utility grid power. The PET hence restores the system frequency by adjusting supply and demand at the PCC. The micro-grid can now participate in frequency regulation for the main grid. The simulation results are obtained to verify the operation and claims of the dynamic power limiter as stated below: 1. Restricted active power flow to the micro-grid, at a desired value determined by the main utility grid. 2. Utilization of the change in local grid frequency, to dynamically control the active power generation or consumption within the micro-grid. 3. Decentralized control of the DERs as well as the controllable loads, which operate synchronously, to supply the demand within the micro-grid. 4. Bi-directional active-power flow capability at the PCC. 5. Voltage regulation by control of reactive power. 6. Contribution of the micro-grid components in frequency regulation of the main grid. 7. Smooth transition from islanding to grid-connected mode of the micro-grid, without the need of grid synchronization. 8. Extra degree of freedom due to the presence of active-power controller in a possible deregulation and market strategy within the micro-grid.
Keywords/Search Tags:Power, Micro-grid, Transformer, Strategy, PET, Regulation
Related items