A study of a desuperheater heat recovery system complete with a reversibly used water cooling tower (RUWCT) for hot water supply

Posted on:2001-04-15Degree:Ph.DType:Thesis
University:Hong Kong Polytechnic (People's Republic of China)Candidate:Tan, KunxiongFull Text:PDF
GTID:2462390014952993Subject:Engineering
Abstract/Summary:
Recovering heat rejected from the condenser in a refrigeration system to generate service hot water for buildings is commonly seen in both tropics and subtropics. This study included a critical literature review on heat recovery from air-conditioning/refrigeration systems, with particular emphasis on the direct condenser heat recovery and its related mathematical simulation models. The review identified many applications of desuperheaters to small-scaled residential air-conditioning or heat pump units.; The heat and mass transfer characteristics of a RUWCT have been studied in detail, which is based on the theory of direct contact heat and mass transfer between moist air and water. The thesis reports on the differences in the heat and mass transfer process that takes place in a RUWCT, a standard water cooling tower and a spray room. A corrective factor that accounts for the change of chilled water mass flow rate is incorporated into the theoretical analysis of a RUWCT. The algorithms developed from the theoretical analysis are capable of predicting the heat exchange capacity of a RUWCT at any operating conditions. This theoretical analysis is the first of its kind.; Extensive field experimental work on the heat and mass transfer characteristics of a RUWCT has been carried out in a hotel building in Haikou, Hainan province of China, where the RUWCT is installed. Results from the experimental work indicate that the theoretical analysis can represent the heat and mass transfer characteristics in a RUWCT with an acceptable accuracy.; A numerical analysis for a RUWCT is undertaken to determine both air and water states at intermediate horizontal sections along the tower height. Field experimental data confirm that the predicted air and water conditions at the tower inlet and outlet are of acceptable accuracy.; A steady-state mathematical model is developed to simulate the operational performance of a water chiller plant complete with a desuperheater heat recovery system and a RUWCT. This model will be useful in future studies on the optimum design of a water chiller complete with a desuperheater and a RUWCT for heat recovery. (Abstract shortened by UMI.)...
Keywords/Search Tags:Heat, RUWCT, Water, System, Complete, Tower, Mass transfer characteristics, Theoretical analysis
Related items