Font Size: a A A

Generator Microprocessor-based Protection Platform And Its Grounding Protection Improvements

Posted on:2006-06-17Degree:MasterType:Thesis
Country:ChinaCandidate:X M GuoFull Text:PDF
GTID:2192360152990749Subject:Power system and its automation
Abstract/Summary:PDF Full Text Request
This paper propose a new rotor earth-fault protection with switch sampling theory, which sets up three group equations to measure rotor earth-fault resistance. By means of calculation, this paper analyses the partial derivative of earth-fault resistance versus each sampling current at different earth-fault location and under different earth-fault resistance situations, and then draws a conclusion that protection can reduce the influence of sampling current error by selecting different equations to measure earth-fault resistance at different earth-fault location , especially in low exciting voltage and low earth-fault resistance condition。All these are proved by static simulation experiment.
Keywords/Search Tags:Switch sampling theory, rotor earth-fault protection, partial derivative, error